JM Services - шаблон joomla Создание сайтов
  • Measurements m AC and DC
  • Built-in printer for measurements, alarms and microinterruptions
  • Graphic representation of measurements
  • 2 relay alarm outputs
  • RS232 Output
  • High accuracy (class 0,5)
  • Automatic measurement CAMPAIGNS programmed and stored on MEMORY PACK
  • Expandable to other measuring functions using special BLACK BOXES

General Specifications

  • InputsVoltages L1 - L2 - L3 - N: 600 Voltaic between phase and neutral at 20 + 1000 Hz; or 600 Volt CCCurrents L1 - L2 - L3: 1 Voltaic at 20 + 1000 Hz; or 1 Volt CCAuxiliary: AUX 1V/1mA
  • Overload of voltage inputs: Max 720 Vrms - Surge voltage 1200 Volt (a cut-out is tripped at 720 Vrms)
  • Overload of current inputs: 5 times full scale value (with cut-out tripped at limit Values)
  • Number of scales: 4 voltage scales 4 current scales
  • Automatic scale change
  • Scale change response time: 1sec
  • Relay outputs: 2 - Type A- Contacts for 30 Volt / 0,5 A /10 W
  • Instrument dimensions: 240 x 220 x 115 mm
  • Weight 2.25° Kg.
  • Ambient temperature range: +5°C +40°C
  • Safety reference standards: IEC 348, VDE 411 class 2, for operating voltages -650 VAC rms, IEC 1010-1, EN 61010-1, 600V.
  • EMC reference standards: EN 50081-1, EN 50082-1, EN 55022.

Power Supply

  • Mains: 230 ± 10% at 50 Hz or 60 Hz
  • Internal: Rechargeable Ni-Cd battery